We design, supply, install, test and commission the cooling plants of buildings, and maintain the systems we installed: air-cooled and water-cooled chillers, the cooling towers and condenser water systems that reject their heat, thermal energy storage, the energy transfer stations of buildings on a district cooling network, and the pumps, pipework and controls of the chilled water systems that carry the cooling to the air handling units and fan coil units. In the Gulf cooling is the largest load of most buildings, and in a hospital or a data centre it must not stop.
The design starts from the cooling load of each room and of its fresh air, calculated hour by hour for the design day of the site; in Dubai the municipality's design outdoor condition is 46 °C dry bulb and 29 °C wet bulb. We choose the chilled water temperatures, commonly a supply of 6 to 7 °C and a return of 12 to 13 °C, or those a district cooling provider sets, size the plant so that the peak load is met with one chiller out of service, and select the chillers for their efficiency at part load, where they run for most of the year, to ASHRAE 90.1.
We supply the chillers, pumps, heat exchangers and valves, those of the brands we carry among them, and our teams install, pipe and wire them on site. The chilled water and condenser water systems are pressure tested, flushed and chemically cleaned, each chiller is started up by its manufacturer and run against its rated capacity, and the systems are balanced and their controls proved before handover. Under a service contract we then maintain the systems we installed: the chillers serviced to their manufacturers' schedules, their tubes cleaned, the cooling towers cleaned and their water treated and tested.