Earthing and Lightning Protection

Earthing, bonding and lightning protection that carry fault currents and lightning safely into the ground.

We design, supply, install, test and commission the earthing and lightning protection of buildings and their substations, and maintain the systems we installed: the earth electrodes and grids, the main earthing terminals and the protective and bonding conductors, the air terminations, down conductors and earth terminations of the lightning protection, and the surge protective devices that keep a surge out of the electrical and electronic systems.

The design starts from the ground and the building. We measure the soil resistivity of the site by the Wenner method and model the electrodes and grids that reach the earth resistance each system needs; we assess the lightning risk to IEC 62305-2, from which follow the class of the lightning protection system and the surge protection it needs; and we bond every service and every metal part of the building into one equipotential system, to IEC 60364-5-54, BS 7430 and IEC 62305.

We supply the electrodes, the conductors, the clamps, the air terminals and the surge protective devices, those of the brands we carry among them, and our teams install and connect them, from the earth pits in the ground to the conductors on the roof. Before handover we measure the resistance of each electrode and of the whole earth system by the fall of potential method, and the continuity of every down conductor and bond, and record each test point. Under a service contract we then maintain the systems we installed, retesting them at the intervals IEC 62305-3 sets and after any strike.

Earthing systems and bonding

Most of the buildings we design are earthed as TN-S systems from their transformers, with a main earthing terminal at each main switchboard and a protective conductor run with every circuit. The electrodes are copper-bonded steel rods driven to the depth the soil needs, joined by bare copper conductors and ended in inspection pits, with earth enhancing compound where dry desert sand gives a high resistivity. We design for an earth resistance of 1 ohm or less at substations and data centres, and no more than 10 ohms for the lightning protection, as IEC 62305-3 recommends.

Substation earthing is a grid designed to IEEE 80 for the touch and step voltages of the largest earth fault. Every incoming service, water, gas and fire pipes, ducts, cable armour and the steel of the structure, is bonded to the main earthing terminal; data centres and imaging rooms take a mesh bonding network that holds every rack and cabinet at one potential; and in hospitals the group 1 and group 2 locations have supplementary bonding of their own.

Lightning protection and surge protection

The risk assessment sets the class of the lightning protection system, from class I to class IV, and with it the geometry of its air termination: a rolling sphere of radius 20, 30, 45 or 60 m, a roof mesh of 5, 10, 15 or 20 m, and down conductors spaced at 10, 10, 15 or 20 m around the building. We design the air terminations to protect every part of the roof and its plant, use the reinforcement or the steel frame as natural down conductors where it is continuous, and end each conductor at a test joint above its earth.

Surge protection follows the lightning protection zones of IEC 62305-4. Type 1 surge protective devices at the main switchboards, tested with the 10/350 µs impulse of a direct strike, take the lightning current that enters on the incoming lines; Type 2 devices at the sub-main boards and Type 3 at sensitive equipment limit what remains, each to IEC 61643-11 and coordinated with the next.

Systems and equipment

Earthing

  • Earth electrodes: copper-bonded steel rods, copper tape and plates, in inspection pits
  • Substation earth grids: designed to IEEE 80 for touch and step voltages
  • Main earthing terminals: at each main switchboard, with the protective and bonding conductors
  • Earth enhancing compound: for ground of high resistivity

Bonding

  • Main protective bonding: water, gas and fire pipes, ducts, cable armour and the structural steel
  • Mesh bonding networks: for data centres, control rooms and imaging rooms
  • Supplementary bonding: equipotential busbars for group 1 and group 2 medical locations

Lightning protection

  • Air terminations: air rods, conductors and roof meshes to the class of the system
  • Down conductors: dedicated, or natural through the reinforcement or the steel frame, with test joints
  • Earth terminations: ring or rod electrodes for the lightning protection, bonded to the earthing
  • Isolated air terminations: for antennas and roof plant that must keep the separation distance

Surge protection

  • Type 1 surge protective devices: at the origin of the installation, for direct lightning currents
  • Type 2 and Type 3 devices: at the sub-main boards and at sensitive equipment
  • Data and signal line protection: for telephone, data, control and fire alarm lines
  • Photovoltaic surge protection: DC devices for arrays and inverters

Standards we work to

  • IEC 62305: protection against lightning, parts 1 to 4
  • IEC 60364-5-54: earthing arrangements and protective conductors
  • BS 7430: code of practice for protective earthing of electrical installations
  • IEEE 80: guide for safety in AC substation grounding
  • IEEE 81: measuring earth resistivity, ground impedance and earth surface potentials
  • IEC 61643-11: surge protective devices connected to low-voltage power systems
  • IEC 62561: lightning protection system components
  • The regulations of the UAE's electricity authorities, those of DEWA in Dubai among them