Transport Terminals

Rail, metro, bus and coach terminals, stations, depots and control buildings, with ventilation, power and tunnel safety.

The building services of a terminal

A rail, metro, bus or coach terminal gathers crowds that arrive in waves, in concourses, on platforms and at bus bays that are often below ground, with no window to open and no daylight to see by. Its services keep those spaces cool and fit to breathe, hold back the smoke of a fire in the terminal or the tunnel beside it, keep the terminal running when the supply fails, and tell passengers where to go, in normal service and in an emergency. Behind the terminals and their stations stand the depots where the fleets are maintained and the control buildings from which a line or a network is run, each with demands of its own.

We plan a terminal's services with its architects, its operator and the fire engineer, from the flows of passengers at the busiest hour and the fire strategy of the terminal and, for a railway or a metro, its tunnels. Our architects, structural engineers and building services engineers work on one coordinated model. The traction supply, the overhead lines and the railway signalling are the railway's own systems, built by others, and we coordinate ours with theirs. We design to the UAE Fire and Life Safety Code of Practice and the regulations of the UAE's authorities, and to the IEC, EN and NFPA standards each system follows.

We supply the plant and equipment of each system we build, and our teams install it on site. Each system is tested before the terminal opens: the smoke control with the fire alarm through each zone of the cause and effect, the voice alarm for its sound levels and its intelligibility on every platform, at every bus bay and in every hall, every emergency luminaire for its full duration; the civil defence then witnesses the fire systems. Under a service contract we maintain the systems we installed. Each of these systems is described under Disciplines.

Concourses, platforms and bus bays

A terminal must stay comfortable for passengers who wait a few minutes and the staff who work in it all day, while its crowds come and go with the trains, buses and coaches. We cool the concourses, the enclosed platforms and the bus bays' waiting areas with air handling units on chilled water, dry their outdoor air in dedicated outdoor air units before it reaches them, and let carbon dioxide sensors set the outdoor air of the halls to the crowds in them. A terminal below ground has no room to add a plant room or a shaft later, so we fix them with its architects and structural engineers in the first design. We design the escalators to EN 115-1, at no more than 30°, or 35° where the rise is no more than 6 m and the speed no more than 0.5 m/s, and the public lifts to EN 81-70, for the lift contractor who supplies and installs them. The halls and platforms are lit to EN 12464-1, and daylight sensors dim the lighting wherever daylight reaches it.

Tunnel and platform ventilation

Below ground the ventilation of a station or a bus terminal is a life safety system as well as a comfort one. In normal service it brings in outdoor air and carries away the heat of the crowds, the lighting, the equipment and the vehicles at the platforms and bays; in a fire it must keep the smoke away from the people escaping it. With the fire engineer we design the ventilation of a station's platforms and halls to NFPA 130, for each fire the fire strategy considers, in the station and in the tunnels at either end of it, so that the smoke is drawn away from the escape routes and the stairs stay clear. The smoke extract fans are rated to EN 12101-3 for the temperature and time the fire strategy sets, commonly 400 °C for 2 hours, and stair and lobby pressurisation keeps the protected stairs free of smoke. The fire alarm's cause and effect sets each fan and each damper for the zone the fire is in.

Fire and life safety

Passengers on a platform below ground escape upwards, the way smoke also travels, so detection must be early and the alarm clear. We detect fire throughout the terminal's public and technical areas, in zones that follow its levels and compartments, and write the cause and effect with the fire engineer: the ventilation turns to smoke control, the lifts return to their designated floor, and doors on the escape routes unlock. The voice alarm gives alert and evacuate messages in Arabic and English, live announcements come from the fire microphone, and its loudspeakers run on interleaved A and B circuits from amplifiers with a standby, so that one fault silences no area. Emergency lighting to EN 1838 gives at least 1 lux on the centre line of each escape route along the platforms, the bays and the stairs. Standpipes carry water to the hose connections the fire service uses, and fire telephones give firefighters two-way speech to the fire control room, to BS 5839-9.

Power

The trains run on the railway's traction supply, and a terminal's services on a supply apart from it. We design it from its intake, connected to the utility at 11 kV in most of the UAE or to the railway's own medium-voltage network, through its transformers to its main switchboards and essential distribution boards, whose separate sections for the safety services, the critical loads and the rest are fed by standby generators when the supply fails. Loads that cannot accept a break, the terminal's communication systems and control equipment among them, take their supply from online double conversion UPS systems, and the emergency lighting runs from central battery systems to EN 50171, for one to three hours. The cables of the fire pumps, the smoke extract, the fire alarm and the emergency lighting are fire resistant and routed apart from the rest, and the others are low smoke and zero halogen, as wherever people gather. Every incoming service and the steel of the structure is bonded to the building's main earthing terminal, in coordination with the railway's traction earthing.

Depots and control buildings

A depot is an industrial building: long workshop halls with their inspection pits, stores and offices, where the trains, buses and coaches are serviced by day and by night. We give its workshops compressed air, commonly at 7 to 8 bar for plant air, from a ring main that feeds every point from two directions, light its halls and its yards, protect its stores with sprinklers chosen for their hazard, and charge its service vehicles from chargers whose load management shares the depot's spare capacity between them. The control buildings from which a line or a network is run hold equipment rooms that must not stop: we feed them from UPS systems, cool them with split units, duty and standby, bond their cabinets to a mesh bonding network, and protect them with clean agent systems where water would harm the equipment. Their doors are access-controlled, and the security management system brings the access, intruder and camera alarms to one screen in the control room.

Communications

Passengers need to know where to go and when their train, bus or coach leaves, and the staff need to see the whole terminal from one room. The public address is zoned, from horn and column loudspeakers on the platforms, at the bays and in the halls, so that one platform or bay can be called alone, at a level commonly 6 to 10 dB above the background noise, which sensors raise as crowds gather. Announcements are ranked: the voice alarm first, then live announcements from the paging stations, then the automatic announcements of departures. Passenger information comes to the screens from the terminal's own systems, on screens of 2,500 cd/m² or more where daylight falls on them. Each camera is placed under EN 62676-4 for what it must do, 250 pixels per metre at a person to identify them and 125 to recognise them, its views on the video wall of the control room, and in Dubai the CCTV follows the requirements of SIRA. Ticket offices take hearing loops to IEC 60118-4, with 400 mA/m at the listener.

What we hold to in a terminal

The way out stays clear: the ventilation, the lighting and the alarm are designed together for the fire strategy of the terminal and of any tunnel beside it.

Below ground the first design must be complete: every plant room, fan shaft and route a terminal needs is placed in it, since none can be added once the terminal is built.

The terminal is run from one room: its cameras, its alarms and its announcements reach the control room, in normal service and in an emergency.

Systems and equipment

Ventilation and smoke control

  • Air handling units: on chilled water, for the concourses, enclosed platforms and waiting areas
  • Dedicated outdoor air units: fresh air cooled and dried before it reaches the halls
  • Smoke extract fans: rated to EN 12101-3, commonly 400 °C for 2 hours
  • Stair and lobby pressurisation: fans and relief dampers that keep smoke out of the escape routes
  • Split units: duty and standby units in the equipment rooms

Electrical power

  • Substations: the supply of the utility or of the railway's own network stepped down to 400 V
  • Standby generators: for the safety services and the critical loads
  • UPS systems: online double conversion, for the communication and control equipment
  • Fire-resistant cables: for fire pumps, smoke extract, fire alarm and emergency lighting
  • Main protective bonding: every incoming service and the structural steel

Detection, alarm and escape

  • Fire detection: zones that follow the terminal's levels and compartments
  • Voice alarm: alert and evacuate messages in Arabic and English, on A and B loudspeaker circuits
  • Emergency lighting: to EN 1838, at least 1 lux on the centre line of an escape route
  • Standpipes and landing valves: wet or dry risers in the stairs, with fire service inlets
  • Fire telephones: two-way speech for firefighters, to BS 5839-9

Passenger communications

  • Public address: zoned so that a platform or a bus bay can be called alone
  • Passenger information: screens fed from the terminal's own systems
  • CCTV: cameras placed under EN 62676-4, their views on the control room's video wall
  • Hearing loops: to IEC 60118-4, at ticket offices and counters
  • Telephony: an IP exchange with SIP trunks to the telecommunications operators