Structured Cabling and Networks

Fibre backbones, Category 6A cabling to every outlet, and the switches and wireless networks they carry.

We design, supply, install, test and commission the structured cabling and the networks of buildings and campuses, and maintain the systems we installed: the optical fibre backbones between buildings and up the risers, the copper cabling from each floor's equipment room to every outlet, the cabinets, pathways and bonding that hold them, and the switches, routers, firewalls and wireless access points that run on them. One cabling carries a building's data, telephones, cameras, access control, nurse call, IPTV and building management, each on a network of its own.

The design starts from the outlets: how many each room needs and what will plug into them, desks, beds, cameras, access points, displays and controllers, and the power each draws over the cable. From them we place an equipment room on each floor within 90 m of cable of every outlet, size the backbone and the cabinets with room to grow, and route the pathways apart from power cables, to ISO/IEC 11801-1, EN 50173-1 and EN 50174-2, or to TIA-568 and TIA-569 where a project follows American standards. In a hospital we plan the networks with its IT team, those that carry medical devices among them, whose risks the hospital manages under IEC 80001-1.

We supply the cabling, the cabinets and the active equipment, and our teams install, terminate and label them on site. Every copper link is tested to its class with a certification tester and every fibre for its loss, and the results are handed over with the drawings and the labelling records; the switches are configured, and the wireless network is surveyed again once it is installed. Under a service contract we then maintain the systems we installed: the records kept up to date through every move and change, faults traced and links retested, and the software of the active equipment kept current.

Backbone, horizontal cabling and testing

The backbone is optical fibre: single-mode OS2 between buildings and from the building distributor to the floors, with OM4 multimode where the links are short, each cable with spare fibres and spliced into panels at both ends. From each floor's distributor, Category 6A cables run to every outlet as Class EA links of ISO/IEC 11801-1, with no more than 90 m of fixed cable and a channel of no more than 100 m with its cords, so that every outlet can carry 10 gigabit Ethernet. The cables are low smoke and zero halogen, in trays and baskets kept apart from power cables by the separations EN 50174-2 sets.

Each link is tested: copper with a certification tester to its class, for insertion loss, crosstalk and return loss, and fibre with a light source and a power meter and, on long or spliced backbones, an optical time domain reflectometer. Each cabinet has a bonding bar connected to the building's earthing to EN 50310, and every outlet, cable, panel and port carries a label that matches the records.

Switches, wireless and power over the cable

The network is built in layers: two core switches linked to each other, and access switches on every floor connected to both, so that the loss of a core switch or an uplink cuts off no floor. Each system has its own virtual network, the clinical, business, guest, telephone, camera and building management traffic kept apart and joined only through firewalls. Access switches power cameras, telephones, access points and displays over the cable to IEEE 802.3bt, up to 90 W a port, and run with the core from UPS systems, so that telephones and cameras keep working through a power failure.

Wireless access points are placed from a predictive survey and checked on site, commonly for a signal of −67 dBm or stronger where telephones and clinical devices roam, on Wi-Fi 6E or Wi-Fi 7. In the UAE every radio we supply carries the type approval of the TDRA. Data halls are cabled to TIA-942 or EN 50600-2-4, commonly overhead in trays above the cabinets.

Systems and equipment

Optical fibre

  • Campus links: single-mode OS2 between buildings, in ducts with draw pits
  • Riser links: OS2 or OM4 from the building distributor to each floor's equipment room
  • Fibre panels: fusion-spliced pigtails and duplex connectors, with spare fibres at both ends

Copper cabling

  • Outlets: Category 6A to every desk, bed, camera, access point and display
  • Links: Class EA of ISO/IEC 11801-1, with no more than 90 m of fixed cable
  • Patch panels and cords: in each floor's cabinets, coloured by system
  • Consolidation points: for open floors whose furniture will move

Rooms and pathways

  • Equipment rooms: the building distributor, and a floor distributor within 90 m of every outlet
  • Cabinets: with cable managers, power distribution and cooling sized for their load
  • Containment: trays, baskets and conduits, apart from power cables to EN 50174-2
  • Bonding: a bonding bar in each room, connected to the building's earthing to EN 50310

Active network

  • Core switches: two, linked to each other, with every floor connected to both
  • Access switches: power over the cable to IEEE 802.3bt for cameras, telephones and access points
  • Wireless access points: Wi-Fi 6E or Wi-Fi 7, placed from a survey
  • Firewalls and routers: at the edge of the network and between its systems
  • Network management: the monitoring of every switch, port and access point

Standards we work to

  • ISO/IEC 11801-1: generic cabling for customer premises
  • EN 50173-1: information technology, generic cabling systems
  • EN 50174-2: cabling installation, installation planning and practices inside buildings
  • TIA-568: telecommunications cabling for commercial buildings
  • TIA-569: telecommunications pathways and spaces
  • EN 50310: telecommunications bonding networks for buildings and other structures
  • IEC 80001-1: the application of risk management for IT networks incorporating medical devices
  • The regulations of the TDRA, the UAE's telecommunications authority, its type approval of equipment among them