We design, supply, install, test and commission the fire protection systems of buildings, and maintain the systems we installed: automatic sprinklers and their water supplies, fire pumps and tanks, standpipes, hydrants and hose reels, water mist systems, the clean agent and inert gas systems of rooms that water would harm, the suppression of kitchen hoods, and portable extinguishers. The fire alarm that detects a fire and starts these systems has a page of its own under ELV and Automation.
The design starts from the fire strategy and the hazard of each part of the building: the occupancy classification of NFPA 13 or the hazard class of EN 12845, from which follow the design density, the area of operation, the duration of the water supply and the pressure the pumps must give. A hospital is sprinklered throughout with quick-response sprinklers, since its patients are moved from compartment to compartment rather than out of the building. We design to the UAE Fire and Life Safety Code of Practice in the UAE, and to the NFPA or EN standards the authority and the client require elsewhere.
We supply the pumps, valves, sprinklers, pipework and extinguishing systems, those of the brands we carry among them, each listed or approved for its use, and our teams install them on site. Each sprinkler system is hydrostatically tested, under NFPA 13 at 13.8 bar, or 3.4 bar above its working pressure where that is higher, for 2 hours; the fire pumps are run at churn, at their rated flow and at 150 per cent of it; and the rooms of the gaseous systems pass a door fan test for their hold time, before the authority witnesses the systems at handover. Under a service contract we then maintain the systems we installed: valves exercised, pumps run, sprinklers and agent containers inspected at the intervals the codes set.