Government

Ministries, courts and civic buildings, with the security, power and comfort systems of public service.

The building services of civic buildings

A ministry, a court or a civic building serves the public and holds what the state must keep safe: its staff, its records and its proceedings. Its services must let the public in and keep them to the parts they may enter, keep the building at work through a failure of the supply, keep its public halls and offices comfortable for those who wait and those who work in them, and carry every hearing and meeting to those who must hear it, while the building uses as little energy as it can over the many years it stands.

We plan a civic building's services with its architects, its security adviser and the authority that will run it, from the brief of each department and the security plan of the whole. Our architects and engineers coordinate the building on one model, so that the security zones, the plant rooms and the routes of the services are settled together. We design to the UAE Fire and Life Safety Code of Practice and, in Dubai, the requirements of SIRA, with the IEC, EN and ASHRAE standards each system follows.

We supply the plant and equipment of each system we build, and our teams install it on site. Each system is proved before the building opens to the public: every controlled door tested for each way it opens and locks, every camera checked against its purpose, every transfer to the generators tested with the mains switched off, and the sound and recording of the courtrooms and chambers tried in their uses; the civil defence then witnesses the fire systems. Under a service contract we maintain the systems we installed. Each of these systems is described under Disciplines.

Security and access

A civic building is open to the public, but only to the parts the public may enter. A visitor's pass, issued at reception, opens only the zones of the visit and only while it lasts, and turnstiles or speed gates hold the line between the public hall and the offices. We grade each controlled door under IEC 60839-11-1 for what lies behind it; its reader talks to its controller over the secure channel of OSDP, and the controller decides by itself whether a card may open the door, even without the network. In a court, the judges, the staff, the public and the people held in custody come and go by routes of their own, and the access control keeps each to its route. Intruder and hold-up alarms are graded under EN 50131 for the risk of each part, commonly grade 3 for cash offices, and every door on an escape route unlocks on the fire alarm, its release actuated to BS 7273-4.

Standby power

The loads a ministry or a court cannot lose are its security systems, its communications and the rooms where hearings and meetings take place. We design the distribution from the intake, at 11 kV in most of the UAE, to the essential distribution boards that carry them, whose safety, critical and other sections the standby generators feed when the supply fails. Generating sets to ISO 8528, derated for a Gulf site's 50 °C air and its dust, run on fuel stored for the autonomy agreed, and automatic transfer switches to IEC 60947-6-1 move the essential loads between the mains and the generators. The data rooms and the security systems run on online double conversion UPS systems, classified VFI under IEC 62040-3, which carry them without a break while the generators start, with an autonomy of commonly 10 to 30 minutes at full load. We assess the lightning risk to IEC 62305-2, which sets the class of the lightning protection, and surge protective devices to IEC 61643-11 keep a surge out of the electronic systems.

Public halls and offices

A public hall fills and empties with the queues at its counters, while the offices behind it hold the same staff all day, so we serve the two apart. The halls are tall and often glazed: air handling units with variable air volume serve them through jet nozzles or slot diffusers chosen for their throw and noise, and carbon dioxide sensors set their outdoor air, and that of the courtrooms and meeting rooms, to the people in them. The offices take variable air volume too, with fan coil units for the rooms that need their own control, and every room is held at commonly 23 to 24 °C and 50 to 55 per cent relative humidity, its outdoor air cooled and dried in dedicated outdoor air units on the roof. We set the outdoor air rates to ASHRAE 62.1 or EN 16798-1, and light each room, the counters and the desks among them, to the maintained illuminance its tasks need under EN 12464-1.

Fire and life safety

A civic building must bring the public out of a building they do not know, and keep the records it holds. We detect fire in zones that follow its storeys and compartments, a zone covering no more than 2,000 m² on one storey under BS 5839-1, and settle with the fire engineer what each alarm does: smoke control takes over the ventilation, the lifts go to their designated floor, the escape doors unlock and the voice alarm speaks in Arabic and English. Its offices and public areas take quick-response sprinklers, and its archives, whose records water would harm, are protected by inert gas or clean agent systems to NFPA 2001 or ISO 14520, each room proved for its hold time by a door fan test. Visitors who cannot use the stairs wait at refuge points with two-way speech to the fire control room, to BS 5839-9, and the stairs and their lobbies are pressurised to keep the smoke out.

Communications and audio-visual

Courtrooms and council chambers depend on every word being heard, recorded and, more and more often, joined from elsewhere. We design the sound reinforcement of each room for its coverage across the seats to ANSI/AVIXA A102.01, give the bench, the witness stand and the advocates' places microphones with echo cancellation, and record what is said over the network. A camera, and a display sized to ANSI/AVIXA V202.01 for the farthest viewer, let a witness or a party take part by video call. Hearing loops to IEC 60118-4, with a field strength of 400 mA/m at the listener, serve the public seats and the service counters. The telephone system is an IP exchange with SIP trunks to the telecommunications operators, its handsets and radios type-approved by the TDRA, as every one we supply in the UAE is. Category 6A cabling reaches every outlet, and the security, telephone and public wireless networks are kept apart, joined only through firewalls.

Energy efficiency

Many civic buildings were built before the energy regulations that now apply to them, so our work on them often starts from an energy audit to ISO 50002, which finds where the energy goes, at what tariff and in which hours, and which measures pay back within the client's horizon. A new building we design to ASHRAE 90.1 and the authority's green building regulations, Al Sa'fat in Dubai and Estidama in Abu Dhabi among them. Its motors are specified to efficiency class IE3 or IE4 of IEC 60034-30-1, the pumps and fans whose flow varies run on variable speed drives, and photovoltaic arrays on its roofs and car park canopies supply part of its load, their connection approved in Dubai under DEWA's Shams Dubai. Once the work is done, each measure's savings are verified against its baseline, as IPMVP describes, and the meters report by system to the building management system, so that the savings are kept.

What we hold to in civic buildings

The public reaches only what it may: every zone of the building is set by its security plan, and every escape route opens to everyone in an emergency.

Public service goes on through a failure of the supply: the essential sections run on the generators, and what cannot accept a break on UPS systems.

A new building's energy is settled in its design and an existing one's found by audit, and the meters keep it in view once the work is done.

Systems and equipment

Security systems

  • Speed gates and turnstiles: between the public hall and the offices
  • Visitor management: passes issued at reception, valid only for the zones and the time of the visit
  • Door controllers: deciding at the door, with readers on OSDP to IEC 60839-11-5
  • Intruder and hold-up alarms: graded under EN 50131, commonly grade 3 for cash offices
  • CCTV: cameras placed under EN 62676-4, in Dubai to the requirements of SIRA

Electrical power

  • Standby generators: rated to ISO 8528, derated for the 50 °C air and the dust of a Gulf site
  • Automatic transfer switches: to IEC 60947-6-1, between the mains and the generators
  • UPS systems: online double conversion, for the data rooms and the security systems
  • Lightning protection: of the class a risk assessment to IEC 62305-2 sets
  • Surge protection: Type 1, Type 2 and Type 3 devices, each to IEC 61643-11
  • Photovoltaic arrays: on roofs and car park canopies, connected under the utility's rules

Air and comfort

  • Air handling units: variable air volume for the public halls and the offices
  • Air terminals: jet nozzles and slot diffusers chosen for their throw and noise
  • Carbon dioxide sensors: the outdoor air of halls, courtrooms and meeting rooms set by their occupancy
  • Fan coil units: for the rooms that need their own control

Fire systems

  • Fire detection: zones of no more than 2,000 m² on one storey, under BS 5839-1
  • Sprinklers: quick-response sprinklers in the offices and the public areas
  • Gaseous systems: inert gas or clean agent for the archives, proved by a door fan test
  • Refuge points: two-way speech to the fire control room, to BS 5839-9
  • Stair and lobby pressurisation: fans and relief dampers that keep smoke out of the escape routes

Communications

  • Sound reinforcement: coverage to ANSI/AVIXA A102.01 in courtrooms and chambers
  • Recording and video calls: proceedings recorded over the network, and parties joined by video
  • Hearing loops: to IEC 60118-4, at the public seats and the service counters
  • IP telephony: SIP trunks to the telecommunications operators, handsets approved by the TDRA
  • Structured cabling: Category 6A to every outlet, the networks kept apart by firewalls