Medical IT systems that keep operating theatres and intensive care supplied through a first insulation fault.

We design, supply, install, test and commission the isolated power systems of hospitals, and maintain the systems we installed. An isolated power system, the medical IT system of IEC 60364-7-710, supplies the medical electrical equipment of the group 2 locations: the operating theatres, the intensive care and coronary care units, the catheterisation laboratories and the anaesthetic and recovery rooms, where a sudden loss of supply would put a patient's life at risk.

Its isolating transformer separates the circuits of the room from earth, so that a first fault between a conductor and earth raises an alarm instead of tripping the supply in the middle of an operation. We plan the group 2 locations with the hospital, give each theatre or each group of beds a system of its own, place the panels, the alarm indicators and the socket outlets at each patient place, and design the equipotential bonding of each room, to IEC 60364-7-710 and HTM 06-01, or to NFPA 99 and NFPA 70 where a project follows American codes.

We supply the medical IT panels, the isolating transformers, the insulation monitoring devices and the alarm indicators from the brands we carry, and our teams install them in the theatres and the critical care units and connect them to the safety supplies. Each system is tested before the hospital takes the rooms into use: the insulation monitor's alarm at its set value, the transformer's leakage current and its load and temperature monitoring, and the resistance of every bonding connection. Under a service contract we then maintain the systems we installed, with the periodic tests IEC 60364-7-710 asks for.

Medical IT systems in group 2 locations

Each medical IT system starts at an isolating transformer for medical locations to IEC 61558-2-15, single-phase, of 3.15 to 10 kVA, with a secondary voltage of no more than 250 V AC and a leakage current to earth of no more than 0.5 mA, in a panel inside or beside the room it serves. A theatre or a group of intensive care beds takes its own system, so that a fault in one room does not affect another, and its circuits feed the medical electrical equipment of the patient environment.

An insulation monitoring device to IEC 61557-8 measures the insulation resistance of the system all the time and raises an alarm when it falls to 50 kilohms, with a measuring voltage of no more than 25 V DC and a measuring current of no more than 1 mA, even under a fault. The transformer is monitored for overload and for high temperature, and its circuits are protected by double-pole circuit breakers.

Alarms, fault location and equipotential bonding

Every medical IT system has an alarm indicator where the medical staff see and hear it, in the theatre and at the nurse base: a green light while the system is in order, a yellow light and a sound when the insulation resistance reaches its alarm value, the sound silenceable and the yellow light lit until the fault is cleared. Insulation fault location devices to IEC 61557-9 find the circuit with the fault while the system stays in service, so that the technical staff can clear it after the operation rather than during it.

In each group 2 location the protective conductors of the socket outlets and the fixed equipment, and the metalwork of the room, its medical gas pipes and pendants among them, are bonded to an equipotential busbar in or beside the room. We design the bonding so that the resistance between the busbar and each terminal is no more than 0.2 ohms, as IEC 60364-7-710 sets, and measure it at commissioning.

Systems and equipment

Medical IT panels

  • Isolating transformers: single-phase, 3.15 to 10 kVA, to IEC 61558-2-15, with winding temperature sensors
  • Medical IT distribution boards: double-pole circuit breakers with the insulation monitor and the transformer's load and temperature monitoring
  • Theatre panels: recessed in the theatre wall or set in a room beside it
  • Automatic changeover: between two supplies, ahead of the transformer

Monitoring and alarms

  • Insulation monitoring devices: to IEC 61557-8, with the alarm at 50 kilohms
  • Alarm indicators: green and yellow lights with a silenceable sound, in the theatre and at the nurse base
  • Insulation fault location: to IEC 61557-9, finding the faulty circuit while it stays in service
  • Building management interface: the state of each system passed on over Modbus or BACnet

Bonding and the patient place

  • Equipotential bonding busbars: one for each group 2 location, in or beside the room
  • Bonding of extraneous parts: medical gas pipes, pendants, beams and the metalwork of the room
  • Socket outlets at the patient place: fed from more than one circuit, those of the IT system marked as such

Isolated power to American codes

  • Isolated power panels: for wet procedure locations under NFPA 99 and article 517 of NFPA 70
  • Line isolation monitors: an alarm at a total hazard current of 5 mA
  • Receptacles and grounding points: hospital-grade receptacles with their reference grounding points

Standards we work to

  • IEC 60364: low-voltage electrical installations, with part 7-710 for medical locations
  • IEC 61558-2-15: isolating transformers for the supply of medical locations
  • IEC 61557-8: insulation monitoring devices for IT systems
  • IEC 61557-9: equipment for insulation fault location in IT systems
  • HTM 06-01: electrical services supply and distribution
  • NFPA 70: the National Electrical Code, with article 517 for health care facilities