Healthcare

Hospitals with their operating suites, intensive care units, sterilisation departments and laboratories.

The building services of a hospital

In a hospital the building services are part of the care. The air of an operating theatre carries the particles of the operation away from the wound, the medical gases and the power keep patients alive, and the water must reach a patient without the bacteria that grow in it. The services run without a break, through a failure of the mains, a fire in one compartment or work on a part of them, and within a few metres they serve rooms of very different demands: wards, operating suites, intensive care, sterile services, laboratories and the mortuary.

We plan a hospital's services department by department from its clinical brief, with its architects and its clinical staff, so that each room has the air, power, medical gases, water and communication its use requires. We design to the health facility guidelines of the UAE's health authorities, those of the Dubai Health Authority among them, and to the HTM, DIN, EN, IEC and ISO standards each system follows, or to NFPA 99 and the FGI Guidelines where a project follows American codes.

We supply the plant and equipment of each system, and our teams install it on site, the pipelines pressure tested before the ceilings close. Each system is commissioned before the hospital takes it into use: the generators run on a load bank, the theatres measured for their air changes, pressures and airflow, the medical gases tested for identity and purity, and every call point of the nurse call tested from its button to every display and phone it must reach. Under a service contract we then maintain the systems we installed. Each system has a page of its own under Disciplines.

Hospitals

When the mains fail, a hospital's loads come back in their turn, each on a section of its own: under IEC 60364-7-710 the safety services return within 15 s and run for at least 24 hours, or under NFPA 99 and NFPA 110 the life safety and critical branches return within 10 s. Patients are moved from compartment to compartment rather than out of the building, so we detect fire throughout, category L1, as HTM 05-03 Part B asks, stage the alarm for progressive horizontal evacuation and sprinkler the whole hospital with quick-response sprinklers; the fire alarm never shuts off the medical gases. On a seismic site a hospital with surgery or emergency treatment is in Risk Category IV under ASCE 7, and the services it needs to keep operating are braced and anchored for an importance factor of 1.5. The building management system repeats the alarms of the medical gases and the isolated power to the engineers, but never replaces the alarm panels where the clinical staff work.

Operating-room suites

In an operating suite the systems of every discipline meet at one table. Each theatre or suite has an air handling unit of its own, so that work on one does not stop another. Under DIN 1946-4 a room of class Ia has a canopy of low-turbulence displacement flow over the table, commonly 3.2 by 3.2 m, whose H13 or H14 filters supply a stable field of clean air; under HTM 03-01 an ultraclean theatre holds fewer than 10 colony-forming units per cubic metre in its clean zone, and a general theatre takes 25 air changes an hour. The medical electrical equipment runs on a medical IT system, whose first fault to earth raises an alarm instead of tripping the supply, and the luminaires of the operating table return within 0.5 s for at least 3 hours. The pendants carry the medical gases at a nominal 400 kPa and surgical air at 700 to 800 kPa, and the panel on the theatre wall shows the clock, the elapsed time and the room's temperature, humidity and pressure.

Intensive care

In intensive care every patient depends on equipment that must not stop. Each group of beds takes a medical IT system of its own, so that a fault in one room does not affect another, and the metalwork of each bed space is bonded to its equipotential busbar. Ceiling beams and bridges bring the medical gases to the bed and keep the floor around it clear, and an emergency clinical alarm at the nurse base reports the pressure of each gas in the zone. A cardiac arrest call reaches the resuscitation team's phones with the room it came from, ahead of every other call. Airborne infection isolation rooms are held negative to their anteroom and the corridor, by at least 2.5 Pa under ASHRAE 170, with 12 air changes an hour and their exhaust discharged directly outside, above the roof, and a monitor at each door alarms when a door is left open or a fan fails. Where the client wants it, tunable white lighting follows the day and helps patients keep their rhythm of sleep.

Sterilisation

A sterile services department turns used instruments into sterile sets, and its services follow the instruments from the dirty side to the clean. We plan the wash room, the packing room and the sterile store as a line the instruments never travel back along, the air held as a cascade from the cleanest room outwards. The washer-disinfectors take their final rinse, and the sterilisers and clean steam generators their feedwater, from purified water made by reverse osmosis, often followed by electrodeionisation, to the quality HTM 01-01 and EN 285 set. The steam must kill by condensing on the load, and EN 285 and HTM 01-01 set its quality: no more than 3.5 per cent of non-condensable gases by volume, a dryness value of at least 0.95, or 0.9 for metal loads, and no more than 25 K of superheat on expansion to atmospheric pressure. Plant steam carries the boiler's treatment chemicals, so we generate clean steam from purified water in a steam-to-steam or an electric generator, carry it in stainless steel and test its quality at the sterilisers.

Laboratories

A hospital laboratory needs its samples to arrive intact, its water pure and its waste made safe. Pneumatic tubes bring the samples from the wards, the emergency department and the theatres; we set the speed of each route and land the carriers softly, and with the laboratory we validate the system before use, comparing samples sent by tube with samples carried by hand for haemolysis and the analytes it affects, as its accreditation to ISO 15189 expects. Laboratories take water of the grades of ISO 3696: grade 3 for washing and general use, grades 2 and 1, polished at the point of use, for analysis. Laboratory waste passes through a neutralising tank before it joins the rest of the drainage, each laboratory using gas has detectors and an automatic shut-off valve, and the exhaust of containment laboratories passes through bag-in bag-out filter housings. The structure gives the laboratories floors stiff enough for the vibration limits of their equipment.

Mortuaries

A hospital asks of its mortuary that the stores never warm, that the staff work in them safely and that every surface can be cleaned. With the hospital we plan the body stores to HBN 20 or the health authority's guidelines: refrigerated stores at 2 to 4 °C for short-term storage, deep-freeze chambers at −20 °C or colder where a body must be kept for longer, racking loaded by a mechanical hoist and spaces for bariatric bodies. Each store has two refrigeration systems, or a duty and a standby condensing unit, and the building management system passes its temperature alarm at once to the engineers on duty. Every chamber has an alarm push and an inside release for a person shut in, and the post-mortem room is held negative to its neighbours and extracts at the table, to HTM 03-01. Linings of stainless steel or hygienic panels, coved at the corners, and floors falling to a drain make every surface cleanable. The cold rooms and their plant are described under Refrigeration, Cold Rooms and Walk-in Mortuaries.

What we hold to in a hospital

The hospital keeps running through a failure: its plant meets the demand with a unit out of service, and its essential loads have a second supply.

Infection control shapes the services: the air moves from the cleanest room outwards, the cold water is kept cold and the hot water hot, out of the range in which Legionella multiplies, and the fittings of clinical rooms are sealed for cleaning.

The clinical alarms stay where the clinical staff work: the building management system repeats them to the engineers and never replaces them.

Systems and equipment

Electrical power

  • Standby generators: the safety services back within 15 s under IEC 60364-7-710, for at least 24 hours
  • UPS systems: online double conversion, classified VFI under IEC 62040-3, for loads that cannot accept a break
  • Medical IT systems: isolating transformers, and insulation monitors alarming at 50 kilohms, for the group 2 locations
  • Safety supplies for operating theatres: changeover within 0.5 s for the surgical luminaires
  • Clinical lighting: 1000 lux in the operating theatres with a colour rendering index of 90, sealed luminaires in clinical rooms

Air

  • Hygienic air handling units: stainless interiors to VDI 6022 and DIN 1946-4, one for each theatre or suite
  • Unidirectional airflow canopies: low-turbulence supply over the operating table, through H13 or H14 filters
  • Isolation and protective rooms: held negative or positive, with a pressure monitor at each door
  • Cleanroom suites: ISO 14644-1 classes 5 to 8 and EU GMP grades A to D, for pharmacies

Medical gases

  • Sources of supply: a primary, a secondary and a reserve source for each compressed gas
  • Pipelines: seamless copper tubes degreased to EN 13348, at a nominal 400 kPa, or 700 to 800 kPa for surgical air
  • Area valve service units: at the entrance of each zone, with an emergency inlet for each gas
  • Alarms: the operating, emergency operating and emergency clinical alarms of ISO 7396-1
  • Anaesthetic gas scavenging: duplex pumps serving the disposal terminal units of the theatres

Water and steam

  • Hot and cold water: stored at 60 °C or more, 55 °C at every hot outlet within 1 minute, every cold outlet below 20 °C within 2 minutes
  • Thermostatic mixing valves: 41 °C at basins and showers where patients could be scalded
  • Dialysis water: to the quality ISO 23500-3 sets, from two passes of reverse osmosis, in a loop without dead legs
  • Clean steam: from purified water, for the sterilisers and the humidifiers of the theatres
  • Laboratory water: grade 3 of ISO 3696 for washing, grades 2 and 1 polished at the point of use for analysis

Fire and life safety

  • Fire detection: category L1 throughout, as HTM 05-03 Part B asks
  • Staged alarms: the evacuate signal in the compartment of the fire, an alert beside it and a staff alarm elsewhere
  • Voice alarm: a speech transmission index of 0.50 or more in each area
  • Sprinklers: quick-response sprinklers throughout the hospital
  • Seismic restraint: braces and anchors for an importance factor of 1.5 in a Risk Category IV hospital

Hospital systems

  • Nurse call: to DIN VDE 0834-1 and HTM 08-03, cardiac arrest calls first of all
  • Theatre control panels: clock, elapsed time, temperature and humidity set, pressure shown, lighting and intercom
  • Pneumatic tubes: samples to the laboratory and drugs from the pharmacy, validated with the laboratory
  • Bed lifts: class III of ISO 4190-1, commonly 2,000 kg with a car of 1,500 by 2,700 mm
  • Mortuary stores: 2 to 4 °C, and −20 °C or colder, each with two refrigeration systems or a duty and a standby condensing unit